Technical Summary
Application
|
LV and MV ( 208V - 38 kV
|
Configuration
|
Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
|
Modes of Operation
|
Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
|
Generator Protective Devices
ANSI Protective Devices
|
15/25, 27/59, 81 O/U, 32, 40, 50, 51
|
Utility Protective Devices
ANSI Protective Devices
|
15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86
|
Environmental Parameters
Certifications
|
IBS, CBC, UBC & OSHPD Certified
|
Control Panel Enclosure
|
NEMA 1 or NEMA 3R, Freestanding Construction
|
Low Voltage Standards
|
NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
|
Medium Voltage Standards
|
NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
|
Operating Temperature
|
0 degrees to 50 degrees C
|
Storage Temperature
|
-20 degrees C to +60 degrees C
|