Cat Switchgear
More Comfort – More Performance – More Versatility
-
Up To 25% Footprint Savings
Utilizing Unique Systems Level architecture designs
-
Voltage Ratings up to 37.5 kW
Indoor, outdoor & arc resistant gen switchgear designs
-
Control and Information at your fingertips
Systemwide data integration, graphical representation and available connection to site BMS systems for access to all emergency power system status and alarms.
Enclosure Rating
| Configuration | IP4X |
Operating Temperature
| Operating Temperature | 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) |
Dimensions
| Standard Depths | 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers |
| Standard Heights | Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping |
| Standard Widths | 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. |
Technical Summary
| Technical Summary | Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. |
Application
| Application | LV 380…480 VAC, 50 Hz, 3-Phase. |
Modes of Operation
| Modes of Operation | Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. |
Download resources
Tech-Link Switchgear Remote Access System Service Tool
Get info about our financing options
Get The best solution for your job site needs
Let us help.
Enclosure Rating
| Configuration | IP4X |
Operating Temperature
| Operating Temperature | 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) |
Dimensions
| Standard Depths | 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers |
| Standard Heights | Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping |
| Standard Widths | 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. |
Technical Summary
| Technical Summary | Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. |
Application
| Application | LV 380…480 VAC, 50 Hz, 3-Phase. |
Modes of Operation
| Modes of Operation | Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. |