Skip to content
3516C Generator Set

3516C Generator Set

1650 - 2500 ekW Diesel Generator Set

More Comfort – More Performance – More Versatility

  • Over 4,000,000,000 Global Operating Hours

    Proven performance in heavy-duty applications

  • Over 200,000 Shipped

    Since 1981, leading the large engine market

  • BMEP 17% Lower Than Other Brands

    Provides great block load capability and durability

Generator Set Specifications

Duty Cycle Standby, Mission Critical, Prime, Continuous
Emissions/Fuel Strategy U.S. EPA Cert., Tier 2
Frequency 60 Hz
Maximum Rating 2500 ekW
Minimum Rating 1650 ekW
Prime Power Rating 2250/2045/1825 ekW
Speed 1800 rpm
Standby Rating 2500/2250/2000 ekW
Voltage 380 to 13800 Volts

Engine Specifications

Aspiration TA
Bore 6.69 in
Compression Ratio 14.7:1
Displacement 4764.73 in
Engine Model 3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel
Fuel System Electronic unit injection
Governor Type Ademâ„¢3
Stroke 7.48 in
Stroke - HD 8.46 in

Generator Set Dimensions

Dry Weight - Genset (maximum) 38780 lb
Dry Weight - Genset (minimum) 35880 lb
Height - Maximum 118.5 in
Height - Minimum 116.5 in
Length - Maximum 295.1 in
Length - Minimum 284.6 in
Width - Maximum 101.2 in
Width - Minimum 93.7 in

Download resources

Electric Power Ratings Guide
3516C, 60 Hz, 1650-2000 ekW, U.S. EPA Stationary Emergency (Tier 2) Spec Sheet
3516C 60Hz, 2045-2250 ekW, U.S. EPA Stationary Emergency (Tier 2) Spec Sheet
3516C 60 Hz, 2050-2500 ekW, U.S. EPA Stationary Emergency (Tier 2) Spec Sheet
3516C, 60 Hz, Prime-DCP 1825 ekW, U.S. EPA Stationary Emergency (Tier 2) Spec Sheet
3516C 60Hz, Prime-DCP 2045 ekW, U.S. EPA Stationary Emergency (Tier 2) Spec Sheet
3516C 60 Hz, Prime-DCP 2250 ekW, U.S. EPA Stationary Emergency (Tier 2) Spec Sheet